Home Up Contents

HVAC PRIME SOURCE, LLC


Maintenance Tips

 

[Under Construction]

DAMPERS & DUCTING

Tips

Leak check of isolation dampers

It may be difficult to test dampers for leak tightness. It is best to check the damper blade seals to confirm that they are sitting tight against the seat and there are no visible leak paths. This can be done by doing a smoke test at the face of a closed damper with pressure on the other side, or by observing a light shining across the face of a closed damper. If gaps are identified, the actuator and damper blade positioning may have to adjusted for a tight closure or blade seals replaced.

Gravity backdraft dampers

In case of relatively large or critical applications, the blade shaft bearings should be of ball bearing type rather than sleeve bearings.

 